SCAME F200 Fire Rated Isolator Switch 80A 3P+SN — General, Pre-Threaded Entries

Sale price$1,668.95 AUD

Tax included. Shipping calculated at checkout

SKU: 590.F2GE8005.ASN
In stock
Free Standard Shipping

Eligible for Free Shipping Australia Wide on orders above AU$249
*Excludes Large and Bulky Items

Product specifications

YOUR SELECTED MODEL

590.F2GE8005.ASN

The specifications below belong to this product. Use them to confirm the current, pole configuration, protection rating and enclosure dimensions required for your installation.

Download datasheet
Rated current at AC22A
80A
Poles
3P+SN
Protection degree IP
IP66
Protection degree IK
IK10
Material
Die-cast aluminium
Colour
Grey
Dimensions
150x210x107mm
Cable entry
2xM32 drilled and threaded on the bottom

ISOLATORS-FR

Built for critical smoke extraction

Fire-rated switch-disconnectors for smoke extraction applications, including basement car parks and emergency evacuation routes.

The F200 and F400 ranges offer two temperature classifications, with aluminium-enclosure versions from 20A to 160A in the Australian selection guide.

120 minFire-rated duration200°C / 400°CF200 / F400
SCAME fire rated switch disconnector range

SELECT THE RIGHT CLASSIFICATION

F200 or F400?

F200 · 200°C for 120 minutes

Aluminium-enclosure isolators with provision for up to two auxiliary contacts. Australian 20–100A .ASN versions include a solid neutral terminal and pre-threaded bottom cable entries.

F400 · 400°C for 120 minutes

A thermosetting switch provides dimensional stability at high temperature. Aluminium versions are IP65, with provision for one auxiliary contact and blank sides for cable-entry preparation.

Select the fire classification required for the application. Confirm the exact model, electrical duty and installation requirements using its datasheet.

Open fire rated aluminium enclosure showing construction details numbered 01 to 08

MAIN CHARACTERISTICS

Designed around the details

  1. 01

    Blank sides as standard. .ASN versions have pre-threaded bottom cable entries.

  2. 02

    High-visibility, ergonomic XXL handle.

  3. 03

    Emergency handles padlock OFF only. General-use handles padlock OFF with three padlocks or ON with one.

  4. 04

    Door locking with the switch in the ON position.

  5. 05

    Painted die-cast aluminium enclosure with resistance to UV rays and atmospheric agents.

  6. 06

    F400 thermosetting switch material for dimensional stability at high temperature.

  7. 07

    AC23A switching duty, with auxiliary contacts available: up to two on F200 and one on F400.

  8. 08

    Switched-neutral 2P and 4P versions use an early-make / late-break neutral pole. Earth connection uses a terminal or threaded bar.

Illustrated aluminium version. .SN and .ASN codes have an unswitched solid neutral; check the selected model for its configuration.

PLAN YOUR INSTALLATION

Choose, connect and install

Read the part number, compare handle options and plan the enclosure and cable entries.

How to read a part number

590.F2EM6305.ASN

590.

PREFIX

SCAME article

F2

CLASS

F2 = F200, 200°C
F = F400, 400°C
Both for 120 minutes

EM

VERSION

EM = emergency use
GE = general use

63

CURRENT

20–160A
AC22A at 415V

05

POLES

02 = 2P
03 = 3P
05 = 4P (3P+N)
06 = 6P

.ASN

SUFFIX

.ASN = solid neutral + pre-threaded bottom entries (F200 20–100A)

.SN = solid neutral

Emergency vs General handle

Both versions interlock the enclosure door when the switch is ON. Handle padlocking is a separate function.

FeatureGeneral use · GEEmergency use · EM
Handle / plateBlack / greyRed / yellow
OFF padlockingUp to 3 padlocksOFF locking only
ON padlocking1 padlockNot available
Door interlockLocked with switch ONLocked with switch ON

Maximum padlock arch: F200 8mm; F400 6mm for 20–40A and 8mm for 63–160A.

Cable-entry & enclosure guide

Standard enclosures have blank sides. F200 .ASN versions add pre-threaded entries in the bottom face; other faces remain blank.

RangeCurrentDimensions (mm)Bottom cable entries
F20020–40A105 × 150 × 82.ASN: 2 × M25 threaded
F20063–100A150 × 210 × 107.ASN: 2 × M32 threaded
F200125A264 × 315 × 122Blank
F200160A315 × 410 × 150Blank
F40020–40A168 × 192 × 80Blank
F40063–100A217 × 253 × 93Blank
F400125–160A315 × 410 × 150Blank

Catalogue dimensions are a selection guide. Confirm the selected model's drawing before drilling or mounting. Threaded entries do not indicate supplied cable glands.

Auxiliary contacts
RangeMaximum auxiliary contactsSelection
F2002Match the accessory to the installed switch size and required contact operation.
F4001Confirm the compatible accessory against the exact model's documentation.

Capacity does not mean contacts are included. Confirm the accessory code and switching sequence before ordering.

Chemical & environmental guide

SCAME's indicative guide for aluminium enclosures.

AgentResistance
Saline solutionResistant
Concentrated acidsLimited resistance
Diluted acidsResistant
Concentrated basesLimited resistance
Diluted basesResistant
Hexane, benzol, acetone and alcoholResistant
Mineral oilResistant
UV raysResistant

Indicative values only. Confirm suitability for the specific substance and exposure conditions with SCAME technical service.

Source: SCAME ISOLATORS-FR Australian catalogue ZP01354-EN-0, pp. 1–6. Ratings and dimensions vary by model.